DESCRIPTION:
ZHFFR (ZERO Halogen Free Flame Retardant) insulation
105°C | Non-Toxic & Non-Corrosive | Does not propagate flame &
fire
• REACH, ROHS, CE and CPR Compliant
• Anti-Rodent, Anti-Termite
• 100% Electrolytic Copper
• More than 101% Conductivity
Application
These cables are ideal for domestic applications, conduit wiring and
fixed, protected installations. Apart from residential and
commercial properties, these cables are best suited for Auditoriums,
Hospitals, Hotels, Schools, Stadiums and all constructions for
Public usage. These cables are ideal for use in environments where
high-performance, reliability and safety is a norm. also Suitable
for use in conduit and for fixed, protected installation
particularly suitable for wiring in fire and explosion prone areas,
chemical factories, densely wired areas, public buildings, schools,
hospitals, commercial complexes, theatres, etc.
Technical Data
Approvals: IS 17048 marked, FIA/TAC
Cable Code: XZ
Voltage Grade: Up to and including 1100V
Conductor: Strands of electrolytic annealed plain copper are
multi-drawn for uniformity of resistance, dimension and
flexibility.
Insulation: EVA BASE POLYMER
Colours: Green, Black, Red, Yellow, Blue, White
Marking: The cables are marked 'EXTRA SAFE'
Packing: 90 mtrs. Coils packed in protective cartons.
Properties
• Temperature range: -15°C to +105°C
• Max. Short circuit temperature rating: 250°C
• the insulation does not burn readily.
• It does not melt and drip
• Smoke is negligible, transparent, non-toxic
• the victims trapped in fire do not suffocate and this facilitate
firefighting operations.
• The cable has extended service life against the conventionally
used cables.
• The cable is also ozone resistant
• Self-extinguishing and flame retardant according to IS 10810 P -
61
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the
suffix (in place of 'xx') for the colour required
01 - Green, 02 - Black, 03 - Red, 04 - Blue, 05 - Yellow, 06 - White
PRODUCT DETAILS:
Nominal Cross Sectional Area (Sq. mm) |
Nominal Insulation Thickness (mm) |
Number *Nominal Dia. of Strands |
Approx. Overall Diameter (mm) |
Max. DC Conductor Resistance at 20�C (Ω/km) |
Current Rating (Amps) |
|
Casing |
Concealed |
|||||
0.75* |
0.6 |
11/0.3 |
2.4 |
26.00 |
10 |
9 |
1.0* |
0.7 |
14/0.3 |
2.7 |
19.50 |
16 |
15 |
1.5* |
0.7 |
22/0.3 |
3.0 |
13.30 |
21 |
19 |
2.5* |
0.8 |
36/0.3 |
3.7 |
7.98 |
34 |
27 |
4.0** |
0.8 |
56/0.3 |
4.1 |
4.95 |
38 |
31 |
6.0** |
0.8 |
84/0.3 |
4.6 |
3.30 |
50 |
41 |
* As per conductor class 2 of IS 8130
* As per conductor class 5 of IS 8130
Test Parameters for Assessment of Halogen:
Test |
Test Method |
Values |
pH |
IS 17048 |
≥ 4.3 |
Conductivity |
IS 17048 |
≤ 10 �s/mm |
Chlorine and bromine expressed as content of HCL |
IS 10810 P - 59 |
≤ 0.5% |
Presence of fluorine |
IS 17048 |
≤ 0.1% |